ECONTECH T2-CAN CANopen stepper drive communication with delta PLC---Parameter setting
A:PDO setting
Double click node ,will display the dialog as below, the configured PDO details as shown in half bottom of dialog
Note! the default configuration may not be matched with actual application , the user need to configure it base on the actual application

Double click the configured PDO to edit it ,and check the parameters which are from EDS, user can add and delete the parameter

Set the property of PDO

B Automatic SDO configuration
Click the “Automatic SDO configuration” to add and delete the SDO

Note! The input order should be as follow, for example:
Configure the parameter 60FF,set it as 300000,the converted hexadecimal coding is493e0

C Drive parameter setting
Here are some ways to set the parameters of drive
1: Set it via SDO
The parameters of drive can be configured at automatic SDO, just to find the matched address index and data.
2: Send SDO request for setting
Tool→send SDO request

After successfully written, if will show“Write SDO finished!”,and I will show error the written is not successful

3:set it by parameter edit

Modify the value

4:Modify it by program
Change the parameters by SDO written in program(refer the PLC user manual for programming)
D:parameter of drive saving
Write the value 0x65766173 to address 1010+04 for saving the parameter
The below dialog shows error code 03(communication over time),actually , the parameter have been set successfully

E: master setting
Click property of master, will display “:master configuration”dialog. And Configure the synchronizing cycle and heart beat

Double click the master station ,and configure the PDO parameter in node configuration list


Download PDO configuration